Description
Sol-Ark 30K Pre-Wired Hybrid Inverter System is a all-in-one system that includes an inverter, charger controller, a display with remote monitoring. The Sol-Ark is simple to install to a Grid-tied, Off-Grid, or Battery Backup solar system, while being able to manage power to and from Solar, Battery, Grid, Loads, and Generator.
Especially designed for Larger Residential Customers and Light Commercial/Industrial.
Input Data (PV)
Max. Allowed PV Power (STC): 39,000W
Nominal Voltage Range: 150-500V
Startup Voltage: 150V
Max. Input Voltage1: 550V
Max. operating input current per MPPT: 36A
Max. short circuit current per MPPT: 55A
No. of MPP Trackers: 4
No. of PV Strings per MPPT: 2
Max. AC Coupled Input: 57,600W
Output Data (AC)
Nominal AC Voltage (3Φ): 120/208V
Grid Frequency: 50 / 60Hz
Real Power, max continuous (3Φ): 30,000W
Max. Output Current: 83.4A
Peak Apparent Power (7s, off-grid, 3Φ): 45,000VA @ 125A
Max. Grid Passthrough Current: 200A
Power Factor Output Range: +/- 0.8 adjustable
Backup Transfer Time: 5ms (adjustable)
CEC Efficiency: 96.5%
Max Efficiency: 97.5%
Design (DC to AC): Transformerless DC
Stackable: Up to 12 in parallel
Battery Input Data (DC)
Battery Chemistry: Lithium iron phosphate
No. of Battery Inputs: 2
Battery Input Terminal Rating: 50A
Nominal DC Voltage: ≥300V
Operating Voltage Range: 160 – 500V
Battery Capacity Range: 50 — 9900Ah
Max. Battery Charge / Discharge Current: 100A (50A per input)
Charge Controller Type: 3-Stage with Equalization
Grid to Battery Charging Efficiency: 96.0%
Automatic Generator Start (AGS): 2 Wire Start – Integrated
BMS Communication2: CANBus & RS485
General Data
Dimensions (H x W x D): 894 x 528 x 295 mm (35.2 x 20.8 x 11.6 in)
Weight: 79.4 Kg / 172 lb.
Enclosure: IP65 / NEMA 3R
Ambient Temperature: -40~60°C, > 45°C Derating
Noise: < 30 dB @ 25°C (77°F)
Idle Consumption – No Load: 60W
Communication and Monitoring: Wi-Fi & LAN Hardware Included
Warranty: 10 Years
Additional Information
Certifications and Listings (Grid Support Interactive Inverter): UL 1741-2021 (incl UL1741SB), CSA C22.2 No 107.1-16, IEEE 1547-2018 & 1547a-2020 & 1547.1-2020 (SRD V2.0), L1699B, CEC3 , SGIP3
PV DC Disconnect Switch — NEC 240.15: Integrated
Ground Fault Detection — NEC 690.5: Integrated
PV Rapid Shutdown Control — NEC 690.12: Integrated
PV Arc Fault Detection — NEC 690.11: Integrated
PV Input Lightning Protection: Integrated
PV String Input Reverse Polarity Protection: Integrated
Surge Protection: DC Type II / AC Type III
1) See Installation Guide for more details on sizing array strings, the highest input voltage is based on the voltage open-circuit of the array at the minimum design temperature.
2) Active BMS communication is required for all lithium batteries. A list of compatible batteries can be found on our website.
3) Currently pending listing.
Sol-Ark 30K-3P-208V Hybrid Inverter System